Climate-measuring instrument with double display MA 2296 1K
Climate-measuring instrument for room monitoring with display of temperature and
humidity side-by-side. Suitable for computer-based and central data-acquisition, e.g. in
climatic test chambers, climatic rooms, museums, galleries, computer rooms, clean rooms,
and for judging on historical buildings protected and in need for renovation.
By means of the output sockets up to 100 instruments can be networked. This can be done
with special distribution boxes. They can be installed in a distance of 1 km from each
other and can be arranged in a line or radially. Power supply is provided centrally by 1
PSU or locally by a seperate PSU for each instrument.
Using special software, limiting values for temperature and humidity can be specified up
to choice for each instrument.
| Humidity meas. circuit: Measuring range: 5 to 98% r.H. (total range 0 to 100%) |
| Sensor: capacitive thin-film sensor |
| Nominal temperature: 25°C ±3°C |
| Accuracy: ±2% r.H. |
| Reproducability: < 1% r.H. |
| Operating pressure: 0,04 to 20 bar |
| Response time T90: approx. 8 s (without sensor filter) |
|
Temperature meas. circuit: Sensor: NTC type N (10 k at 25°C) |
| Operation range: 20 to +60°C |
|
Accuracy:
30 to 0°C: ± 0,4°C 0 to +70°C: ± 0,1°C |
| Reproducability: 0,1°C |
| Order No. Description | |
|
MA 2296 1K ZB 2290 NA |
Climate-measuring instrument with top hat rail fastening, 1 measuring input for temperature and humidity, 2 output sockets for networking or PC-connection for ONLINE-measurement or OFFLINE-evaluation mains adapter 12 V DC, 200 mA, coaxial connector |
| Option:
OT 2290 HS |
hat rail fastening |
| Recommended temperature/humidity sensors: |
|
|
FH A646 6 FH A646 1 |
ALMEMO®-plug with integrated humidity/temperature sensor 5 to 98% r.H./–20
to +60 °C, Ntc-temperature sensor protection cap and connector made of synthetic material Ø 12 mm, length 87 mm humidity/temperature sensor for climate measurements for seperated arrangement of sensor and instrument 5 to 98% r.H./20 to +80 °C, Ntc-temperature sensor Ø 12 mm, length 162 mm, cable length 1.5m, sensor tube/handle of Alumimium, protection cap SK2 of synthetic material |
|
Networking (for more details see also Data transmission & Networking): |
|
|
ZA 5085 NV ZA 5099 AS ZB 3090 NA ZB 5090 NA2 |
network branch box, input/output RS485 4-wire-bus TX+, TX-,
RX+, RX-, and 2 supply connections, output: ALMEMO®-current-loop galv. sep. all
connection can be clamped
or plugged, power supply by means of DC/DC-converter from
measuring instrument or
bus, with ALMEMO®-cable, length 2 m
RS485 network driver RS232-RS422/RS485, not galvanically separated, input: RS232 9-pol. D-sub, output: RS422/485 4-wire TX+, TX-, RX+, RX- with connection cable, length 2 m mains adapter for: 2 branch boxes/instruments 12 V/200 mA 16 branch boxes/instruments 12 V/800 mA |