Pitot Tubes  The air velocity measured by pitot tubes is calculated by the dynamic and
the static pressure. Pitot tubes are suitable for applications with rough ambient
conditions. They are available in versions of nickeled brass or stainless steel. Pitot
tubes are connected via silicone hoses to a pressure cell and then to ALMEMO®
instruments.
| Specifications for FD-A6x2-Mx |
Accuracy
(zero point aligned) |
± 0.5% (0.2 typically) of full scale |
| Nominal temp. |
22°C ± 3°C |
| Position sensivity |
± 5 Pa; position independant (FD-A602-M1K) |
| Overload |
max 3-fold measuring range |
| Max com-mode pres. |
300 kPa (3 bar) |
| Operating range |
-10 to 60°C, 10 to 90% R.H. not condensing |
| Dimensions |
37 x 36 x 22 mm |
| Hose connections |
5 mm dia., length 12 mm |
| Measuring ranges |
FD-A602-M6: ± 6800 Pa, differential
pressure (2 to 90 m/s*),
measuring values in m/s, Pa
FD-A602-M1: ± 2000 Pa, differential pressure (1 to 40 m/s*),
measuring values in m/s, Pa
FD-A602-M1K: ± 1250 Pa, differential pressure (1 to 40 m/s*),
measuring values in m/s, Pa, position independant
FD-A612-MR: ± 1 bar, dynamic pressure measuring values in mbar |
| * using ALMEMO® instruments for exact
measurements in m/s, the wind channel temperature can be entered for compensation. |
| With automatic temperature compensation for pitot
tubes |
FD-A622-M6: 2 to 98% m/s**; measuring
value:°C, m/s
FD-A622-M1: 1 to 40% m/s**; measuring value:°C, m/s |
| ** the measuring modules with automatic
temperature compensation are suitable for stationary measurements of the wind velocity at
currently changing temperatures. All ALMEMO® NiCr-Ni temperatures sensors can be used.
These measuring modules can only be used for measurements of the wind velocity, but not
for pressure measurements. |

| Order No. |
Description |
| |
Dia. d |
Dia. D |
Length |
Max°C |
FD-9912-33MS
FD-9912-33VA
FD-9912-54MS
FD-9912-54VA
FD-9912-56MS
FD-9912-56VA
FD-9912-84MS
FD-9912-84VA
FD-9912-88MS
FD-9912-88VA
FD-9912-96MS
FD-9912-96VA
FD-9912-97MS
FD-9912-97VA
FD-9912-98MS
FD-9912-98VA
FD-9912-99MS
FD-9912-99VA |
3 mm
3 mm
5 mm
5 mm
5 mm
5 mm
8 mm
8 mm
8 mm
8 mm
10 mm
10 mm
10 mm
10 mm
10 mm
10 mm
20 mm
20 mm |
6 mm
6 mm
8 mm
8 mm
8 mm
8 mm
8 mm
8 mm
8 mm
8 mm
10 mm
10 mm
10 mm
10 mm
10 mm
10 mm
20 mm
20 mm |
300 mm
300 mm
400 mm
400 mm
600 mm
600 mm
400 mm
400 mm
800 mm
800 mm
800 mm
800 mm
1000 mm
1000 mm
1500 mm
1500 mm
2000 mm
2000 mm |
150°C
300°C
350°C
500°C
350°C
500°C
350°C
500°C
350°C
600°C
350°C
600°C
350°C
600°C
350°C
600°C
350°C
600°C |
| (MS =Nickel-plated brass) (VA =Cr-Ni-steel) |
| Accessories |
| ZA 9020 VK2 |
extension cable, length 2m (for FD 622, NiCr-Ni compensation
lead obligatory) |
| ZA 9060 VK2 |
extension cable, length 2m (not for FD 622) |
| ZB 2295-S |
1 set silicone tubes black/colorless, length 2 m |
| ZB 2295-SSL |
silicone tube black per m |
| ZB 2295-SFL |
silicone tube colourless per m. |
{Back} |